D1030
Tie Down Engineering
255 Villanova Drive SW
Atlanta, Georgia 30336
(404) 344-0000 • Fax (404) 349-0401
www.tiedown.com
Example of a Single Section 14' x 62' Home
WIND ZONE III for Single Section Homes
Using Vector Dynamics Foundation Systems
Soil Classifications: 2, 3, 4A & 4B
Soil Bearing Capacity: 1,000 PSF Minimum
Anchors Required: 30"with2-4"helixanchors(#59095)with1-1/4"verticalties
Vector
Systems
Longitudinal
(LSD)
Longitudinal
(LSD)
Anchors
Wind Zone III
NOTES:
Vector Systems should be spaced as symmetrical as possible along
the length of the home. Pier spacing must be consistent with home
manufacturers instruction and/or state requirements.
Maximumallowable working load for metal strut: 3150 lbs.
1
One Longitudinal Vector System is made up of 2 struts,
which can be used separately.
Home Length Vector Systems Anchors Required Longitudinal
Required Per Side Systems
1
(LSD)
0 to 54’ 6 6 2(4Struts)
55’ to 63’ 7 7 2(4Struts)
64’ to 72’ 8 8 2(4Struts)
73’ to 90’ 9 9 2(4Struts)
21 Revised: 8/19/08